Darryl Friar commenced his career 1994 in New Zealand as a Fire Systems Designer and then proceeded to broaden his skill set by working as a Estimator and then Project Manager. This experience lead him into a Senior Role as a Consultant for four years with one of New Zealand's leading Fire Protection Consultancy Firms. Darryl’s experience is unique and sets him apart from other designers. He is a
13/12/2024
Freezer's and Cool rooms 4 deg C or less require a sprinkler called a Dry Drop or Dry Barrel Sprinkler.
This type of Sprinkler doesn't allow the water to enter the pipe until there bulb (element) pops. If we used standard sprinklers the water would freeze in the pipe behind the sprinkler.
Often in supermarkets in the back of house area they put there chillers and freezers under the mezzanine (usually offices/lunch room on top) to utilise space.
Often they will design it so that the refrigeration panel is hard too or as close to the slab above as possible.
If Sidewall dry drops cant be used, the ceiling panel needs to be dropped to allow for the installation of the dry drop sprinkler.
Spotting these little issues early on in the design development stage is this key. There is no point waiting for the contractor to tell them as they are going to construction that it is not going to work.
13/12/2024
Explaining to architects about the 1m clearance required in a fire stair becomes very repetitive. A drawing/picture is worth a 1000 words.
13/12/2024
Combined Hydrant and Sprinkler System.
Break Tanks & Diesel Pump Set.
Residential Apartments near the beach, basement car park.
First 3 floors Designed and Fabbed, Five more floors to go.
13/12/2024
This Warehouse required concept design and is now progressing to Building License. 13,000 sq m. 2 Storey Office, Diesel Pump Set, 504 kl Water Tank.
13/12/2024
This one is 2 Warehouse sharing combined Water Supplies.
Warehouse 1 is 20,000 sqm and has Five 2 storey offices.
K22.4 (32m) sprinklers @ 350 kPa.
Warehouse 2 is 7,260 sqm and has One 2 storey office.
K16.8 (24m) sprinklers @ 350 kPa.
Four systems and 532 kl Fire Tank.
System 1 has just finished Fabrication.
13/12/2024
11,000 sq m Warehouse halfway through construction.
System 1 Fabricated, System 2 to go.
K16.8 (24m) ESFR, Diesel Pump Set & 395 kl Fire Tank.
13/12/2024
Small Warehouse at Brisbane Airport well underway.
K25.2 (36m) @ 410 kPa. Diesel Pump Set, 650 kl Fire Tank.
13/12/2024
Building License drawings done for a New Warehouse.
K16.8 (24m) Sprinklers in 4200 sq m Warehouse.
Two Storey office and Small Canopy.
13/12/2024
Preliminary Consultant Design Started on a Eight Storey Student Accommodation building.
Combined System with Pumps & Tanks, OH2 in Basement Carpark, OH1 for Ground Floor, Residential Floors 1-7 then OH1 for Gym and Pool on Roof.
03/12/2024
Rapid Fire Design proudly supports The Emergency Service Volunteers
Click here to claim your Sponsored Listing.
Location
Category
Contact the business
Telephone
Address
Perth, WA
6122
Opening Hours
| Monday | 7am - 5am |
| Tuesday | 7am - 5am |
| Wednesday | 7am - 5am |
| Thursday | 7am - 5am |
| Friday | 7am - 5am |
| Saturday | 7am - 12pm |